Primary tabs

FREE SHIPPINGFree shipping on all orders over 100000 INR.

ALKALINITY Titration Method for Boiler & Cooling Water

0
No votes yet
SKU::RXSOL-62-5515-002

Product Qty Per Unit: 
1.00
Product usage unit: 
Full SET

Negotiate Price

Generic Name: 
Lab Testing method not suitable for on site testing, But this method is more accurate and scientifc
Product Description: 

ALKALINITY Titration Method for Boiler & Cooling Water ( TITRIMETRIC METHOD 0-200 PPM )

The presence of alkalinity in a water sample may be due to many different substances.  However, for the sake of simplicity, the presence of bicarbonate, carbonate, and hydroxide ions is commonly considered as alkalinity.  The points of change in colour of phenolphthalein and methyl orange indicators, which occur at pH 8.3 and pH 4.3 provide standard reference points which are almost universally used to express alkalinity.

Very high alkalinity values can be undesirable in an industrial water supply.  For example, the presence of a high methyl orange alkalinity should be avoided in boiler feed water because of the resultant carbon dioxide content of the steam.  Carbon dioxide usually is responsible for the corrosion of steam and return lines.  High boiler water alkalinities are also undesirable because the presence of high hydroxide ion concentration is the primary cause of caustic metal embrittlement. A very high boiler alkalinity can also lead to an undesirable carryover condition.  On the other hand, the alkalinity of boiler water must be sufficiently high to protect the boiler metal against acidic corrosion and to ensure precipitation of scale forming salts.  Usual treatment approaches include setting both a minimum alkalinity level and an operating range.
 

Hydroxide alkalinity may be determined by adding barium chloride prior to titration to precipitate the carbonate ion from solution, allowing direct titration of the hydroxide alkalinity.  Measurement of hydroxide alkalinity is also used to control lime soda softeners.

In cooling water systems, alkalinity is of major importance since the total alkalinity of a water is one factor that must be considered when predicting the tendency for the water to precipitate calcium carbonate scale.  Depending on the choice of chemical treatments to protect against corrosion and scale formation, the operating alkalinity and pH ranges are chosen to balance these two features.

Water Testing Procedures Manual ( Full Range Lab testing   Methods with standard  composition ratio Of Reagents  ::: Available with us  at 2700 INR or 54 US$ or 207 AED

Product Application: 

Alkalinity Titrimetric Method (0-200 ppm) 

Principle Theory

This test is based on the determination of alkalinity by titration with standard acid to the phenolphthalein color change (or to a pH of 8.3) and to the methyl orange color change (or a pH of 4.3).  For determination of hydroxide alkalinity only, barium chloride is added prior to titration to precipitate the carbonate ions.  Titration is then taken only to the phenolphthalein end point.  A pH meter may be used instead of the indicators to determine the end points of the titration.

Apparatus Required

Buret 25 ml - 1
Porcelain Cup, 210 ml    -  1
Glass stirring rod      -  1
Graduate,  50 ml - 1
Pipet, delivery, 5 ml      -  1
(1 pH meter- optional)      

 

Chemicals Required

Barium Chloride, 10%
Hydrochloric Acid, 0.02N
Methyl Orange Indicator
Methyl Purple Indicator
Phenolphthalein Indicator
Sulfuric Acid, 0.02N. 

QUICK HANDY ON SITE TEST can be obtaine through   our EASY to USE METHOD ::: RXSOL-62-5515-001 

Product Procedure: 

Testing Procedure

Phenolphthalein (P) and Methyl Orange (M) Alkalinity.

Measure 50 ml of sample into a graduated cylinder and transfer to the casserole.  Add four or five drops of phenolphthalein indicator.  If P alkalinity is present, the sample will turn red.  Add standard 0.02N sulfuric acid from the buret, drop by drop, until the last trace of red color is removed by a single drop.  Record volume of titrant added as the P alkalinity reading. 

Add four drops of methyl orange indicator (if no red color developed on the addition of the phenolphthalein indicator, proceed directly to this point) Continue adding acid dropwise until a change in color from yellow to salmon pink occurs.  Record the total volume (including titrant added for the P reading) as the M alkalinity.  In some cases where the methyl orange color change may be difficult to detect, methyl purple indicator may be used in place of the methyl orange.  The methyl purple color change is from green to gray to purple, with the endpoint being the first change to a definite purple. 

In place of indicators, a pH meter may be used for the titration.  The P alkalinity reading is taken to be the volume of titrant required to bring the solution to a pH 8.3 while the M reading is taken as the volume required to bring the pH to 4.3.  The pH meter should be calibrated prior to use according to manufacturers instructions.  The buffers used for standardization should be within the 4.3 to 8.3 pH range. 

Hydroxide Alkalinity 

Measure 50 ml of sample into  the  graduated  cylinder and transfer to the casserole.  Using the pipet, add 5 ml of barium chloride and stir vigorously.  Add four to five drops of phenolphthalein indicator and stir.  If the sample does not turn red, hydroxide alkalinity is not present.  If the sample turns red, add 0.02N hydrochloric acid dropwise until the color changes from red to colorless.  Record the volume of titrant delivered.

Results Calculation FORMULA :::   

ppm alkalinity (as CaCO3) =   ml 0.02N sulfuric acid         x     1000  /    ml sample 


(for hydroxide alkalinity substitute ml 0.02N hydrochloric acid for ml 0.02N sulfuric acid) Using a 50 ml sample, the alkalinity becomes ml of acid titrant multiplied by 20. 

Product Note: 

Limitations of Test

Phenolphthalein (P) and Methyl Orange (M) Alkalinity

The alkalinity measured from the titration to phenolphthalein end point or P alkalinity is considered to be equivalent to the sum of all the hydroxide ion present plus one half of the carbonate ion present.  The total alkalinity by titration to the methyl orange endpoint or M alkalinity includes the other half of the carbonate ion plus any bicarbonate that was originally present.  The presence of phosphate, silica, organic or other buffers may affect the titration and the calculation of the form of alkalinity present may be in error.    

The presence of bases other than hydroxide, carbon and bicarbonate will interfere directly.
Common bases titratable by acids include sulfide (S=  ) , hydrosulfide ( HS- ), cyanide ( CN-)  and ammonia (NH3) . All these will add to the apparent concentration of one or more of the alkalinities .

measured.  Care should be exercised in interpreting alkalinities found in these water strictly in terms of scaling tendency.  However, under normal circumstances in plant control, expression of result only as the P and M alkalinity actually determined is satisfactory and is preferred from the standpoint of simplicity. 

Hydroxide Alkalinity

The method for hydroxide alkalinity is considered accurate only to within 10 per cent.  High silica, organic matter and aluminates can interfere with the determination, as will the bases mentioned above.  High sulfate content in the sample can produce turbidity which may mask the endpoint.  However, the method for hydroxide alkalinity is satisfactory for routine control and can be valuable in the control of lime-soda softening. 

Product Technical Specification: 
Product pack size: 
Product alias: 
Articles: 
Remarks: 

Apparatus Required

Buret 25 ml - 1
Porcelain Cup, 210 ml    -  1
Glass stirring rod      -  1
Graduate,  50 ml - 1
Pipet, delivery, 5 ml      -  1
(1 pH meter- optional)      

 

Chemicals Required

Barium Chloride, 10%
Hydrochloric Acid, 0.02N
Methyl Orange Indicator
Methyl Purple Indicator
Phenolphthalein Indicator
Sulfuric Acid, 0.02N. 

ALKALINITY Titration Method for Boiler & Cooling Water manufacturer supplier distributor in Mumbai, Kandla, Kolkata, Vizag, Chennai, India, Fujairah, Dubai, Sharjah, UAE, Gulf, Middle East, Muscat Oman, Kenya Africa. Get the best quality of ALKALINITY Titration Method for Boiler & Cooling Water at a competitive price from us. We have ready stock of ALKALINITY Titration Method for Boiler & Cooling Water in India, UAE Gulf, Oman, Kenya Africa. Contact us for bulk as well as small orders.


Product Delivery Locations: 
Kattupalli Port ( L & T Shipbuilding Limited shipyard ), Ennore Port ( Coromondel International Limited Port Area ), Chennai Port, Mugaiyur port, Thiruchopuram port, Silambimangalam Shipyard, Parangipettai port, PY-03 Oil Field, Kaveri port, Vanagiri port, Thirukkadaiyur port, Thirukkuvalai port, Punnakkayal port, Udangudi port, Manappad port, Koodankulam port, Chettinad Tharangambadi Port, Mathur SIDCO Industrial area, Sipcot Industrial Park Malayambakkam

Product Articles

  • FREE SHIPPINGFree shipping on all orders over 100000 INR.
  • MONEY BACK GUARANTEE100% money back guarantee.
  • ONLINE SUPPORT 24/7We are always available for support.

Top Rated Products